Sludge dewatering polymer reduction on a centrifuge
Sludge dewatering polymer reduction was the goal at a Yorkshire wastewater treatment works dosing heavily with polymer on its dewatering centrifuges. The works could not simply dose less: cutting polymer risked floc loss, cake dryness had to be held near 21% to feed the thermal hydrolysis plant, and centrate quality had to stay within process limits. During an October to November 2018 trial, one HydroFLOW® i160 was fitted to the incoming sludge feed pipe before polymer injection on centrifuge 3. Polymer use fell by 11% on matched centrifuge runs, while cake dryness and centrate TSS stayed within acceptable operating limits.
The Challenges
- Sludge dewatering polymer reduction was needed, with high dosing on the centrifuges
- Any cut in polymer dosing risked floc loss
- Cake dryness had to stay near 21% to feed the thermal hydrolysis plant (THP)
- Centrate quality had to remain within process limits
The Solution
- Unit installed: one HydroFLOW® i160
- Installation point: incoming sludge feed pipe, before polymer injection on centrifuge 3
- Trial: October to November 2018 on centrifuge 3, using matched runs
The works needed sludge dewatering polymer reduction, so the unit was fitted to the sludge feed pipe on centrifuge 3, ahead of polymer injection. Less polymer was used with the HydroFLOW® unit during matched runs, and switching it off quickly caused visible loss of flocculation. Cake dryness and centrate TSS stayed within acceptable operating limits, and higher differential RPM on the treated line indicated lower centrifuge stress.