Walla Walla: Scale Returned When the Unit Was Off

Home 9 Case Studies and Results 9 Walla Walla: Scale Returned When the Unit Was Off
Key results
8 weeks with no new drum scale
Pan deposits hose-removable
Scale returned after switch-off

Case Study from HydroFLOW USA

Struvite scale prevention tested on and off at Walla Walla

Struvite scale prevention was tested at the City of Walla Walla Waste Water Plant by switching treatment on, then off, on the same metal. Two 12 x 12 inch sections of the belt press drum and pan were chiselled back to bare metal, and a HydroFLOW® Custom 1 inch unit was installed on 31 May 2013. With it running, the cleaned drum section took no new scale for eight weeks and the pan deposits softened enough to wash off with a hose. With it off, pan scale returned within four weeks, and by seven weeks the drum carried an eighth of an inch and the pan a quarter inch.

The Challenge

  • Struvite scale prevention had to be tested directly against untreated regrowth on the same equipment
  • Hard deposits covered both the belt press drum and pan
  • Deposits were firmly bonded to the metal surfaces
  • Each 12 x 12 inch test section needed a chisel to expose bare metal
  • Limited water flow around the drum restricted deposit removal

Belt press drum surface before and after HydroFLOW, struvite scale cleared from drum holes at Walla Walla WWTP

The Solution

  • Unit installed: one HydroFLOW® Custom 1 inch unit
  • Installed: 31 May 2013, signal verified at 41.2 V peak-to-peak
  • Trial: inspections at five and eight weeks on, then four and seven weeks off

Struvite scale prevention was judged against untreated regrowth on the same equipment. The drum and pan sections were chiselled clean and the unit was switched on. The sections were inspected after five and eight weeks with the unit running, then after four and seven weeks with it deliberately switched off, so the same metal served as both the treated and the untreated surface.

Key Outcomes

R

The cleaned drum section stayed free of new scale for eight weeks of treatment

R

Softened pan deposits washed off with a hose after eight weeks

R

Pan deposits softened enough for clear finger marks after five weeks

R

With the unit off, an eighth inch of drum scale and a quarter inch of pan scale returned within seven weeks

Independent Verification

All results in this study were measured and verified by third-party facilities managers and technical staff.

Summary

With the signal on, the cleaned drum section stayed free of new scale for eight weeks and the pan deposits softened enough to show clear finger marks after five weeks. With it off, a quarter inch of hard pan scale returned within seven weeks. Most trials compare a treated unit against an untreated one. Walla Walla compares the same metal with the signal on and off, which is why it is the post to send to anyone who asks whether the effect is real.